2.2
Mounting to quarter turn
actuators
2.2.1

Preparation of the valve actuator

5
90° / OPEN
The actuator must be in the zero position
(actuator vented).
Remove the screw 5 which retains the
optical position indicator.
Determine the turn direction of the actuator
(seen from above the turn direction of the
actuator must be anticlockwise, when the
actuator moves from the „CLOSED" to the
„OPEN" position).
2.2.2

Assembling the travel sensor

Before mounting the travel sensor to the
actuator, make sure that the shaft height
and the hole pattern in the actuator match
the dimensions of the mounting bracket 6.
6
View X with mounting bracket and adapter
The travel sensor shaft 7 is marked. If this
marking corresponds with the marking at
the bottom of the travel sensor housing 8,
the travel sensor is in the 0° position.
7
Travel sensor with marking
1436 cPos eco
0° / CLOSED
45°
90°
8
View X only travel sensor
The electrical turn range is 90° clockwise
of this position.
Place the adapter 9 on the shaft of the
travel sensor 7.
7
9
Screw the positioner 1 or the travel
sensor 4 onto the mounting bracket 6.
View X
12 / 20
eco
OPEN
ERROR
CLOSED
POWER
1
9
6
4
9
6

Werbung