Wiring of X1 and X4
Option 1 (highly recommended): with wire-end ferrule
• Strip down the conductor to 18mm
• Crimp the conductor with a tubular wire end ferrule with 18mm length of the sleeve
(the conductive part)
• Insert the conductor in the LUF terminal until the end touch the bottom (you will
listen a "click")
Option 2: without wire-end ferrule
• Strip down the conductor to 18mm
• Press to open the clamping point
• Insert the conductor in the LUF terminal until the end touch the bottom (you will
listen a "click")
NOTE: in both cases, to remove the cable, press the release lever till the end to open the
spring and then remove the cable.
(*) It is also allowed to use ultrasound welded conductors. On this case, obviously it is
not necessary a wire-end ferrule, but you might follow the process described in option 1.