GLLI_N/VMF-E4 CONNECTION
Connect the VMF-E4 to the GLLI_N thermo-
stat; this connection must be made using a
4-pole shielded cable (maximum length 30
Characteristics of the cable to be used
for the connection:
• EIB Bus cable,
4 poles + shield;
• Mutual max capacity 100nF/km
(800Hz);
• Resistance max 130 ohm/km;
Key:
A = 4-pole shielded cable (not supplied) for connec-
tion between VMF-E4 and GLLI_N;
B = Shield folded on the cable for earth connec-
tion;
C = Clamp made of plastic conductive material
(supplied) to be fixed on the metallic structure of
the fan coil;
D = Poles to be connected to the interface con-
trol board (supplied) with the GLLI_N card
meters); connect the terminals on the back
of the VMF-E4 to the supplied control board,
and complete the connection by inserting
1
2
1 2 3 4 5 6
1 2 3 4 5 6
the connector plug in the dedicated termi-
nal on the GLLI_N card (as shown).
3 4