Start-up
Danger! High voltage: this sym-
bol warns of high voltages which
may result in injuries to persons
and/or damage to equipment. The
text beside this symbol describes,
where appropriate, options for
avoiding this hazard.
General warning: this symbol
warns of non-electrical dangers,
which may result in serious or
even fatal injuries to persons and/
or damage to equipment. The
text beside this symbol describes,
where appropriate, options for
avoiding this hazard.
Warning of electrostatic dis-
charge: this symbol warns of
electrostatic discharges which
may result in damage to equip-
ment. The text beside this symbol
describes, where appropriate, op-
tions for avoiding this hazard.
General instructions
• This short start-up routine is referenced to
Chapter 5 Connection diagram of this pub-
lication.
• Safety instructions - see at the beginning
of the chapter.
• Recommendations for motor and field volt-
ages (see System description / Operating
instructions ).
• In accordance with DIN 57 100 Part 727 /
VDE 0100 Part 727, precautions must be
taken to enable the drive to be shut down,
e.g. in the event of danger. The unit's binary
inputs or the control panel are not sufficient
as the sole measure for this purpose!
Parameter entry
Examples for entering parameters:
501
= Enter rated motor voltage (sys-
tem-dependent value)
11202
= SAVE MOT1 SET (select setting)
1201
= ARM. AUTOTUNING (select set-
ting)
taken from/for further information:
Operating instructions
3ADW000055 - chapter 2
• Check unit for any damage!
• Install unit, and wire it up
• Supply voltage level / Rated value correct for electronics and fan?
• Supply voltage level / Rated value correct for armature-circuit con-
verter?
• Supply voltage level / Rated value correct for field supply?
• Wiring / cross-sections, etc. correct?
• EMERGENCY STOP functioning properly?
• If a serial interface is to be used for exchanging data with the unit, then
first the optical link between the power converter and the field bus
adapter must be disconnected by withdrawing the cables at V260.
• Connect the electronics power supply
• 522 = English
• 501 = Rated motor voltage
• 502 = Rated motor current
• 507 = Rated line voltage
• In the case of units above 2050 A: see Operating Instructions Manual
• Switch on power via ON/OFF input
• Is the phase sequence correct (no F38 indication)?
• Alter 506 if necessary
Uncontrolled field
with: SDCS-FEX-1
• 505 = DIODE FIELD
EXCIT
• Switch off power via ON/OFF input
• 11202 = SAVE MOT1 SET (save setting)
• 1201 = ARM. AUTOTUNING
• Switch on power via ON/OFF input
• Start drive via RUN input within the next 20 s.
If NOT ACTIVATED appears in the
panel, this means the action has
been completed correctly; stop the
drive; if armature current is flowing
nevertheless, increase value of the
nmin signal (2201).
• Switch off power /drive via inputs
• 11202 = SAVE MOT1 SET (save
setting)
3ADW000177R0222_DCS500B_QuickGuide_ru_b
1 Preparations
2 Standardising signals inside the unit
3 Presetting the field supply unit
Controlled field with:
SDCS-FEX-2
DCF 503A / 504A
• 505 = FEX2 OR FEX3
• 503 = Rated motor
field current
• 1305 = Underexcita-
tion signal
4 Autotuning current controller
If a different text appears in the
display, this means the action has
not been completed correctly.
Operating Instructions Manual
see
Controlled field with:
DCF 501B /
DCF 502B
see Operating Instruc-
tions Manual
I 15