MASTERVISION MODULAR SWITCHBOARDS
CAUTION
1. Lethal voltages exist on your vessel. Make sure all shore power, onboard
generating sources and batteries are disconnected before beginning
installation of your electrical panel.
2. AC modules will have lethal voltages on the bus bars and terminals. The
coating on these bars is for identification only and should not be relied on as a
insulator. Additional safety enclosures may be required in some installations.
3. Make sure all AC modules are bonded to the shipís AC ground bus. When
grouping modules together to form your panel, a single ground may be used.
Use a resistance meter to verify ground to all modules.
The standard remote panel
The standard remote panel is a useful power device for
remote control of the Mass an IVO smart Mastervolt
battery chargers. The standard remote control does indicate the
status of the charge control by six high power leds and control
the output current by setting the potential meter. The remote
control is easy to install by a plug-in standard twisted six pole
RJ45 telephone plug between the digital rs232 output of the
charger and the panel. The serial communication of the remote
control and the charger is based on rs232 technology.
The remote panel can be used as an interface for a custom
made panel or for a dual remote indicator.
The standard remote panel has a CSI (csi=charger
status interface) and a DC high/low alarm.
The two potential free change-over contacts indicate if the
charger is ON or in general failure. The DC alarm set
points can be adjusted in the charger by use of the
adjustment interface.
Specifications
Remote cable:
Connector
RJ45, 6 pole, male
Max length
6 meter, max
Type
twisted wire
External led drive:
Imax
5 mA
Umax
2,5V
External current control
R pot cc
0..1kOhm 0..100%
General CSI alarm
Max rating
1 Amp, 30 VDC
NC-on
When the charger is off or the charger is in
failure, the normally closed contact is closed
C
Common
NO-on
When the charger is on and no-failure is
indicated the normally open contact is closed
DC-high/low alarm (combined function with CSI)
Max rating
1 Amp, 30 VDC
NC-on
When there is no DC failure, the normally
closed contact is closed
C
Common
NO-on
When there is a DC failure the normally open
contact is closed
Connectors
0,75 mm2
48
SPECIFICATIONS
description:
type:
dimensions panel (wxh):
panel depth:
Charger Control
on - bulk charge
external
current control
DC alarm
normally closed
normally open
common
CSI alarm
normally closed
normally open
common
6 pole telephone jack
RJ 45
CSI failure
Bat TC failure
Battery temperature sensor out of range <20 C & >60 C
Voltage sense failure
Voltage sense out of range >3 VDC
Sys. temp. failure
Charger is out of temperature range "overload" (>75--85 C)
Short break indicator
Charger in reduced current mode (short break mode)
Uout <4..5VDC
DC alarm
Battery range out of range (with standard setting of charger)
September 1999 / MASS 12/30, 24/15 and 24/25 battery charger / EN
panel code
part number
07-04-03040
remote standard charger control
for Mass & IVO smart chargers
120 x 65 mm
40 mm
float
absorption
current output
failure
external LED failure
external LED bulk
external LED 20-40%
external LED absorption
external LED 60-80%
external LED float
charger
12V
24V
DC low on
10.0
20.0
DC low off
11.0
22.0
DC high on
16.0
32.0
DC high off
15.0
30.0
Delay time
30
30
C-3-RS
VDC
VDC
VDC
VDC
SEC