Herunterladen Diese Seite drucken

Data Sheets; Technical Specifications - Mastervolt MASS 24/15-2 Betriebsanleitung

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

11
DATA SHEETS MASS 12/30-2
MAIN INFORMATION
Design
: by MASTERVOLT
Manufacturer
: ISO 9001 certified
Model / name
: MASS 12/30-2
Product
: battery charger/rectifier
Article no
: 04-00-10300
Colour
: • RAL 5021, wasserblau
• RAL 7037, grey
Weight excl. packing
: 2.6 kg
Shipping weight
: 4 kg
Cabinet typ
: MASS 1 cabinet
Dimensions
: hxwxd. 325 x 220 x 111 mm
Carton dimensions
: hxwxd. 350 x 250 x 160 mm
Type of packing
: carton recycable
Available
: 230V / 50-60Hz
Availability
: normally from stock, from July '99 onwards

TECHNICAL SPECIFICATIONS

Function apparatus
Nominal input voltage
Input voltage range full specs : 190..250V, 50/60 Hz, ± 5%
Input voltage range no-defects : 0..250V, 33-80 Hz
Input current
Inrush current
Power factor
Max. input power
Efficiency
Output voltage
Output current
Charge characteristic
Kind of batteries
Charge voltage 25°C
Return Amps
Min. Absorption time
Max. Bulk/abs. time
Return new cycle voltage
Temperature compensation
Voltage sense
Ripple voltage
Voltage accurancy
Current accurancy
Maximum output
DC leakage drain
Number of outputs
AC/DC connections
Jumper selections
Remote indication
Remote connection
Temperature connection
Smart controls
Apendix A
: charging of 12V lead acid batteries and power simultanously loads
: 230V AC, 1ph, 3wire, 50/60 Hz
: at 230V AC: 2.5A
: no inrush current, soft start, according to IEC 1003-3
: 1, power factor controlled, IEC 555-2
: 550 Watt
: > 88%
: nominal 12V DC
: nominal 30 Amps
: three-step, fully automatic, IUoUo, programmable
: open & sealed lead acid batteries
: • bulk voltage 14.40V
• wet float 13.25V
• gel float 13.8V
: 2.5A
: 15 minutes
: 6 hours
: 12.8V, delay 30 seconds
: 30 mV/°C, by temperature sensor
: fully automatic compensation
: max. 100mV rms, resistive load, full power
: voltage ± 2%
: current ± 3%
: • 30 Amps at 14.25 Volt at 25°C ambient
• 30 Amps at 13.25V at 40°C ambient
: < 10 mA
: one main outputs and one 3 Amps Slave Charger
: internal,
min. AC cable size: 2.5 mm
: • gel/wet battery selection
• forced to float
• battery isolator compensation
: status bulk, absorption, float
: by telephone plug-in jack - RJ45
: by telephone plug-in jack - RJ45
: QRS232 output by telephone plug - RJ45
Mass 12/30-2 battery charger/rectifier, art.no 04-00-10300,
• absorption 14.25V
2
/ min. DC cable size: 16 mm

DATA SHEETS

in new 'high tech' enclosure.
float charge 80 - 100 %
absorption
50 %
bulk charge - on
off
on
charge failure
2
MASS
AUTOMATIC
BATTERY CHARGER
Standard control on unit.
35

Quicklinks ausblenden:

Werbung

loading

Diese Anleitung auch für:

Mass 24/25-2Mass 12/30-2