8
Appendix
8.3
Interface XS10 PLC, Robot
Pin no.:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
The internal power supply on Pin 8 and 15 is intended for reading in external dry contacts. It is
rated for a maximum of 50 mA.
Do NOT connect a power supply or heavier loads to these outputs!
The optocoupler inputs can be connected to +24 V or alternatively to ground.
The corresponding counter potential is connected for all inputs of this interface
together to Pin 14.
The optocoupler outputs can be supplied for the query with internal or
external (5-24 V DC) voltage. They switch through the potential applied
to Pin 9 (max. 50 mA).
Example: Input externat voltage, positive rail switched
Function
Output: Device ready for dosing
Reserved, do not assign!
Output: fault
Reserved, do not assign!
Start X input
Start Y input
Internal ground output
Input: Potential
Input: Reset fault
Start Z input
Output: Refill tank
Output: Tank empty
Input: Potential
Output: internal +24V supply
Addition
Optocoupler output
Optocoupler output
Optocoupler input
Optocoupler input
for all outputs
Optocoupler input
Optocoupler input
Optocoupler output
Optocoupler output
for all optocoupler inputs
57