OEG KSW-E series Bedienungsanleitungen Seite 40

Differenzregler
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

Para-
Function
meter
F2.17 SWITCH-ON IMPUL-
SE / CIRCULATION
PUMP RUNNING
TIME
F2.18 SWITCH-ON
DELAY / CIRCULA-
TION PUMP
STANDBY TIME
F2.19 MIN/MAX
TEMPERATURE
LIMITATION
F2.20 SENSOR FOR MIN/
MAX TEMPERATU-
RE LIMITATION
Service settings manual
Parameter description
This function activates output for setted time. After setted time
expires, the output is switched off, regardless to other switch-
on or switch-off commands.
This setting is especially useful for control of support pump in
Drain-back systems.
Setting 0 means there is no delay and the output should
activate immedately and stay activated for the whole time of
switch-on command.
This function delays activation of output for setted time. Output
is activated when setted delay time expires.
REMARK: If delay time is longer as time of switch-on period
the output won't activate.
Setting 0 means there is no delay and the output should
activate immedately and stay activated for the whole time of
switch-on command.
Setting if controller should respect min. and max. temperature
limitations of certain sensor by control of output. This function
is usefull by thermostatic operation of output, where min. and
max. temperature limitations of particular sensor should also
be respected.
Selection of sensor for the MIN/MAX limitation.
Setting range
0 ÷ 3600 s
0 ÷ 3600 s
0- NO
1- MIN OFF
2- MAX ON
3- MIN OFF & MAX ON
4- MIN ON
5- MAX OFF
6- MIN ON & MAX OFF
1- T1 2- T2
3- T3 4- T4
5- T5 6- T6
42
Default
value
0
0
0
5