MARKING AND DESCRIPTION OF TEMPERATURE SENSORS

TABLE: Resistance values for temperature sensors type Pt-1000
Temperature
Resistance
[°C]
[W ]
-20
922
-15
941
-10
961
-5
980
0
1000
5
1020
10
1039
15
1058
20
1078
25
1097
30
1117

FLOW METER INSTALLATION

The flow meter is installed in
the return pipe of the solar
system. When installing the
flow meter please refer to the
user manual that is included.
After installing the flow meter
you have to set operation
parameters in the function
parameters W.
Temperature
Resistance
[°C]
[W ]
35
1136
40
1155
45
1175
50
1194
55
1213
60
1232
65
1252
70
1271
75
1290
80
1309
85
1328
47
Temperature
Resistance
[°C]
[W ]
90
1347
95
1366
100
1385
105
1404
110
1423
115
1442
120
1461
125
1480
130
1498
135
1515
140
1536
Temperature
Resistance
[°C]
[W ]
145
1555
150
1573
155
1592
160
1611
165
1629
170
1648
175
1666
180
1685
185
1703
190
1722
195
1740