Table with description of parameters
Para-
Function
meter
S1.1
HYDRAULIC SCHEME
S1.2
CODE FOR UNLOCKING THE
SERVICE SETTINGS
S1.3
TEMPERATURE SENSOR
TYPE
S1.4
TEMPERATURE ROUND UP Precision of displayed temperatures.
S1.5
PERIOD OF TEMPERAT.
LOGGING
S1.6
ADVANCED DISPLAY OF
TEMPERATURES
S1.7
AUT. SHIFT OF CLOCK TO
SUMMER / WINTER TIME
S1.8
ANTI-BLOCK FUNCTION
S1.9
INVERTED OPERATION OF
OUTPUTS
S1.10
TONES
S1.13
SENSOR T1 CALIBRATION
S1.14
SENSOR T2 CALIBRATION
S1.15
SENSOR T3 CALIBRATION
S1.16
SENSOR T4 CALIBRATION
S1.17 SENSOR T5 CALIBRATION
S1.18 SENSOR T6 CALIBRATION
Parameter description
Selection of hydraulic scheme.
This setting enables the change of code which is necessary
to unlock the service settings (S and F parameters).
WARNING! Keep new code on a safe place. Without this
code is impossible to change service settings.
Selection of temperature sensors Pt1000 or KTY10.
By setting this field you define how often the measured
temperatures are saved.
Advanced display of temperatures displays temperatures on
main screen in double rows. First row is measured tempera-
ture; second row is required or calculated temperature.
With the help of a calendar, the controller carries out the
automatic clock changeover between summer and winter
time.
All outputs that haven't been activated in the last week are
activated on Friday at 20:00 for 10 seconds.
Setting of inverted operation for outputs. Invertion of output is
possible only if operation mode of output is ON/OFF
(S3.1=0).
By setting this field you define whether key pressing is
accompanied with sound signals or not.
Correction of displayed measured temperature for sensor T1. -5 ÷ 5 °C
Correction of displayed measured temperature for sensor T2. -5 ÷ 5 °C
Correction of displayed measured temperature for sensor T3. -5 ÷ 5 °C
Correction of displayed measured temperature for sensor T4. -5 ÷ 5 °C
Correction of displayed measured temperature for sensor T5. -5 ÷ 5 °C
Correction of displayed measured temperature for sensor T6. -5 ÷ 5 °C
31
:
Setting range Default
depends on type
of controller
0000 - 9999
0- PT1000
1- KTY10
0- 0.1 °C
1- 0.2 °C
2- 0.5 °C
3- 1 °C
1 ÷ 30 min
0- NO
1- YES
0- NO
1- YES
0- NO
1- YES
0- NO
1- R1
2- R2
3- R1, R2
4- R3
5- R1, R3
6- R2, R3
7- R1, R2, R3
0- OFF
1- KEYPAD
2- ERRORS
3- KEYPAD &
ERRORS
value
201
0001
0
2
5
1
1
0
0
1
0
0
0
0
0
0