Herunterladen Inhalt Inhalt Diese Seite drucken

Scope Of Delivery; Unit Description - Benning PV 1 Bedienungsanleitung

Photovoltaiktester
Vorschau ausblenden Andere Handbücher für PV 1:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

-
after being subjected to rough transport
-
the device is exposed to moisture.
In order to prevent danger
-
do not touch the bare measuring probe tips of the measuring leads,
-
plug the leads into the correspondingly marked jacks at the measuring
instrument
Maintenance:
Do not open the tester, because it contains no components which can be
repaired by the user. Repair and service must be carried out by qualified
personnel only!
Cleaning:
m
Regularly wipe the housing by means of a dry cloth and cleaning agent. Do not
use any polishing agents or solvents!
3.

Scope of delivery

The scope of delivery for the BENNING PV 1 comprises:
3.1 One BENNING PV 1,
3.2 One transport/ storage case
3.3 Two safety measuring leads with probe tip (L = 1.2 m) (red/ black)
3.4 Two safety crocodile clips (red/ black)
3.5 Two safety measuring leads for MC4 connector (red/ black)
3.6 Two safety measuring leads for "Sunclix" connector (red/ black)
3.7 Six 1.5-V-batteries/ type AA (IEC LR6)
3.8 One short instructions
3.9 One CD-ROM with detailed multilingual operating manual and information material
Parts subject to wear:
-
The BENNING PV 1 is provided with two fuses for overload protection:
One fuse with a nominal current of 500 mA, F, 1000 V, breaking capacity ≥ 1000 A, D =
6.3 mm, L = 32 mm (P.no. 749771)
-
The BENNING PV 1 is supplied by six 1.5 V batteries/ type AA (IEC LR6).
Note on optional accessories:
-
AC/ DC current clamp adapter BENNING CC 3 for connection to the BENNING PV 1. The
measured AC/ DC current values can be stored in the memory of the BENNING PV 1 and
can be recalled (part no. 044038).
-
40 m measuring leads BENNING TA 5 with practical rewinder and supporting loop. Connec-
tion: 4 mm safety test socket/ plug (P.no. 044039)
-
Test badges "next test", 300 pieces (P.no. 756212)
-
Test certificate forms for "Testing of PV systems" are available for download free of charge
at www.benning.de
4.

Unit description

See figure 1:
Appliance front face
See figure 2:
Top side of the device
See figure 3:
Digital display
The display and operator control elements specified in Fig. 1, 2 and 3 are designated as follows:
1 Digital display, indicates the test progress and individual measuring results,
-key, for testing the protective conductor resistance
2
R
PE
-key, for starting the automatic PV testing procedure according to VDE 0126-23 (DIN EN
3
Auto
62446)
-key, for carrying out a null balance of the measuring lead resistances
4
NULL
-key, for selecting the testing voltage for insulating resistance measurement
V
5
ISO
-key, for calling stored measured values (display values)
6
-key, for storing the displayed measured values (display values)
7
8 + PV test socket (red), for connecting the red safety measuring lead with PV connector
9 – PV test socket (black), for connecting the black safety measuring lead with PV connector
 – 4 mm test socket (black), for connecting the safety measuring lead with probe tip/ alliga-
tor clip
K + 4 mm test socket (red), for connecting the safety measuring lead with probe tip/ alligator
clip
A R
voltage polarity indication, indicates the polarity of the DC voltage at the 4 mm test
PE
sockets  and K. For AC voltage, "+" and "–" are displayed alternately.
Current clamp measurement enabled
B
09/ 2011
BENNING PV 1
13

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis