8 Diagnosis, asset management and service
Code
Cause
Text mes-
sage
•
F260
Error in the
calibration
Error in the
carried out in the
calibration
factory
•
Error in the
EEPROM
•
F261
Error during
setup
Error in the
•
False signal
configuration
suppression
faulty
•
Error when
carrying out a
reset
•
F264
Adjustment not
within the vessel
Installation/
height/measu-
Setup error
ring range
•
Max. measuring
range of the
instrument not
sufficient
•
F265
Sensor no lon-
ger carries out a
Measure-
measurement
ment function
•
Operating vol-
disturbed
tage too low
Function check
Code
Cause
Text mes-
sage
•
C700
A simulation is
active
Simulation
active
34
Rectification
•
Exchanging the
electronics
•
Send instrument
for repair
•
Repeat setup
•
Repeat reset
•
Check or correct
installation and/
or parameter
settings
•
Use an instru-
ment with bigger
measuring
range
•
Check operating
voltage
•
Carry out a reset
•
Disconnect ope-
rating voltage
briefly
Tab. 8: Error codes
and text messages,
information on
causes as well as
corrective measures
Rectification
•
Finish simulation
•
Wait for the
automatic end
after 60 mins.
Tab. 9: Error codes
and text messages,
information on
causes as well as
corrective measures
Out of specification
Code
Cause
Text mes-
sage
•
S600
Temperature of
the electronics
Impermissib-
in the non-
le electronics
specified range
temperature
•
S601
Danger of ves-
sel overfilling
Overfilling
Maintenance
Code
Cause
Text mes-
sage
•
M500
The data could
not be restored
Error during
during the reset
the reset "de-
to delivery
livery status"
status
•
M501
Hardware error
EEPROM
Error in the
non-active li-
nearisation
table
•
M502
Hardware error
EEPROM
Error in the
diagnostics
memory
•
M503
The echo/noise
ratio is too small
Measu-
for reliable
rement
measurement
reliability too
low
•
M504
Hardware defect
Error at a
device inter-
face
VEGAPULS WL S 61 • 4 ... 20 mA
Rectification
•
Check ambient
temperature
•
Make sure
that there is no
further filling
•
Check level in
the vessel
Tab. 10: Error codes
and text messages,
information on
causes as well as
corrective measures
Rectification
•
Repeat reset
•
Load XML file
with sensor data
into the sensor
•
Send instrument
for repair
•
Send instrument
for repair
•
Check installa-
tion and process
conditions
•
Clean the
antenna
•
Change polari-
sation direction
•
Check connec-
tions
•
Send instrument
for repair