Herunterladen Inhalt Inhalt Diese Seite drucken

Communication Profile Area; Index 1000 To 1Fff - IFM Electronic Ecomat 100 CR2033 Bedienungsanleitung

Ein-/ausgangs-modul
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Communication Profile Area; index 1000 to 1FFF

Index
S-Idx
Designation
2000
11
Configuration
analogue input
channel pair 5/6
12
Configuration
analogue input
channel pair 7/8
2001
0
Frequency
20F0
0
Setting of the
20F1
Node ID
20F2
0
Setting of the
20F3
Baud rate
The entries 20F0/20F1 and 20F2/20F3 must always contain identical values.
The new entries are valid after a reset (switching the module off/on).
Values outside the permissible ranges will be rejected.
*)
Observe hex-code switch position!
Entries under 20F0/20F1 and 20F2/20F3 are only valid if the hex-code switches for baud rate (S1)
and/or node ID (S2, S3) are in the position "F".
(for position and coding of the hex-code switches see page 34)
Type
u8, rw
u8, rw
PWM
u8, rw
u8, rw
*)
u8, rw
*)
C
OMPACT
Default
Description
0x03
0 = OFF
3 = voltage 0...10 V
6 = ratiometric
7 = current 0...20 mA
9 = voltage 0...32 V
A = binary input
with analogue evaluation
B = binary input
with analogue evaluation
with diagnosis
0x03
0 = OFF
3 = voltage 0...10 V
6 = ratiometric
7 = current 0...20 mA
9 = voltage 0...32 V
A = binary input
with analogue evaluation
B = binary input
with analogue evaluation
with diagnosis
0x64
Setting in Hz (20...250 Hz)
(100 Hz)
If an invalid value is entered, the
previous value remains valid.
0x20
The node ID used to access the module
(= 0d32)
in the CANopen network.
0x04
Baud rate of the CAN network
0 = 1000 kBaud
1 = 800 kBaud
2 = 500 kBaud
3 = 250 kBaud
4 = 125 kBaud (default)
5 = 100 kBaud
6 =
50 kBaud
7 =
20 kBaud
M
M
CR2033
ODULE
ETAL
PAGE
41