Startup

Burner adjustment data

Type
Burner power
Low-
Full-
load
load
140
G 04.570
160
VARIO
180
200
The above adjustment data correspond to the default settings. Pre-delivery adjustment settings appear within a black
rectangle. These settings allow the burner to be run in normal operation, but always carry out a careful check of adjustment
settings, as individual plant conditions may require certain corrections.
Dimension
Y
Low-load
(mm)
Cam IV
410
20
470
30
540
30
570
40
Adjusting the gas pressure switch
· Remove transparent cover.
· Provisionally adjust air-pressure
switch to minimum setting.
Adjusting the air-pressure switch
· Remove transparent cover.
· Provisionally adjust air-pressure
switch to minimum setting.
03/2005 - Art. Nr. 13 018 086A
Air-flap opening
Full-load
Cam I
20
45
20
50
20
60
25
60
Frequency controller display
Low load
Full load
(Hz)
(Hz)
40
48.5
40
51
40
55
41
55
EN
37