Herunterladen Inhalt Inhalt Diese Seite drucken

Checking / Setting; Burner Head For Natural Gas / Propane Gas - elco Vectron G 04.570 VARIO Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation

Checking / Setting

Burner head for natural gas / Propane gas

6
40
Adjust the radial flame tube position.
After releasing the three S fixing
screws, the flame tube position can be
adjusted using the H lever. Nitrogen
emissions can be affected by the flame
tube position. Basic setting for scale
value 1.
Fitting burner head
· Place O-ring J in the groove of the
gas connection flange (O-ring is
located in the gas flue of the burner
housing).
· Install the burner head.
· Secure cover (3 screws S in twist and
lock).
· Insert the ionisation probe from the
terminal box into the support.
· Connect ignition cable to ignition
transformer.
03/2005 - Art. Nr. 13 018 086A
Check the burner head
· Check adjustment settings of ionisation
probe 1 and ignition electrode 2 as per
specifications given.
· Check the clearance between twist ring
6 to the burner head.
Conversion to propane gas operation
· Remove gas diffusor 3 and turbulator 4.
· Turn the cover plate 5 by 180° so that
the slots in the turbulator are closed.
· Refit turbulator 4 and gas diffusor 3
(label points to gas pipe).