Herunterladen Inhalt Inhalt Diese Seite drucken

Sicherheitshinweise Für Die Installation Nach Ul Oder Ur - Lenze EVS9321 Montageanleitung

Vorschau ausblenden Andere Handbücher für EVS9321:
Inhaltsverzeichnis

Werbung

2
Sicherheitshinweise
Sicherheitshinweise für die Installation nach UL oder UR
2.4
Sicherheitshinweise für die Installation nach U
J
Warnings!
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
20
Motor Overload Protection
– For information on the protection level of the internal overload protection
for a motor load, see the corresponding manuals or software helps.
– If the integral solid state motor overload protection is not used, external or
remote overload protection must be provided.
Branch Circuit Protection
– The integral solid state protection does not provide branch circuit
protection.
– Branch circuit protection has to be provided externally in accordance with
corresponding instructions, the National Electrical Code and any
additional codes.
Please observe the specifications for fuses and screw−tightening torques in
these instructions.
EVS9321 … EVS9326:
– Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 480 V maximum.
– Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 480 V maximum. When protected by CC, J, T or R
class fuses.
– Maximum surrounding air temperature: 0 ... +55 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.
EVS9327 … EVS9329:
– Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 480 V maximum.
– Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 480 V maximum. When protected by J, T or R class
fuses.
– Maximum surrounding air temperature: 0 ... +55 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.
EVS9330 … EVS9332:
– Suitable for use on a circuit capable of delivering not more than 10000 rms
symmetrical amperes, 480 V maximum.
– Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 480 V maximum. When protected by J, T or R class
fuses.
– Maximum surrounding air temperature: 0 ... +55 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.
l
oder U
L
R
EDKVS9332X DE/EN/FR 4.0

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis