9300
Rated current
Type
I
[A]
r8
EVS9321−xx
1.5
EVS9322−xx
2.5
EVS9323−xx
3.9
EVS9324−xx
7.0
EVS9325−xx
13.0
EVS9326−xx
23.5
EVS9327−xx
32.0
EVS9328−xx
47.0
EVS9329−xx
59.0
EVS9330−xx
89.0
EVS9331−xx
110
EVS9332−xx
145
Bold print = Lenze setting
1)
Switching frequency of the inverter
2)
The currents apply to a periodic load change cycle with max. 1 minute overcurrent duration and 2 minutes base load
duration at max. 75 % I
3.3.2

Operation at 480 V

Basis of the data
Supply
3/PE 480 V AC
DC 678 V (alternatively)
Output voltage
With mains choke
Without mains choke
EDKVS9332X DE/EN/FR 4.0
1)
8 kHz
Maximum
Standstill current
2)
current
I
[A]
I
[A]
M8
08
2.25
2.3
3.75
3.8
5.85
5.9
10.5
10.5
19.5
19.5
35.3
23.5
48.0
32.0
70.5
47.0
88.5
52.0
133.5
80.0
165
110
21.5
126
r
Voltage
[U
]
320 V − 0 % ... 528 V + 0 %
r
[U
]
460 V − 0 % ... 740 V + 0 %
DC
3 ~ 0 ... approx. 94 % U
3 ~ 0 ... U
l
Technical data
Operation at 480 V
Output currents
Rated current
I
[A]
r16
1.1
1.8
2.9
5.2
9.7
15.3
20.8
30.6
38.0
58.0
70.0
90.0
45 Hz − 0 % ... 65 Hz + 0 %
r
r
Rated data
1)
16 kHz
Maximum
Standstill current
2)
current
I
[A]
I
[A]
M16
016
1.65
1.7
2.7
2.7
4.35
4.4
7.8
7.8
14.6
14.6
23.0
15.3
31.2
20.8
45.9
30.6
57.0
33.0
87.0
45.0
105
70.0
135
72.0
Frequency
˘
˘
˘
125