Herunterladen Inhalt Inhalt Diese Seite drucken

Assignment Of Mains Choke/Mains Filter - Lenze EVS9321 Montageanleitung

Vorschau ausblenden Andere Handbücher für EVS9321:
Inhaltsverzeichnis

Werbung

Installation to UL
Supply conditions
Range
Fuses
Cables
Observe all national and regional regulations!
9300
Type
Operation with mains choke/mains filter
EVS9331−xx
EVS9332−xx
5.7.4

Assignment of mains choke/mains filter

9300
Mains choke
Type
EVS9331−xx
ELN3−0027H105
EVS9332−xx
ELN3−0022H130
EDKVS9332X DE/EN/FR 4.0
Standard devices in the power range 55 ... 75 kW
Description
l
Only according to UL 248
l
Mains short−circuit current up to 10000 A
l
Mains short−circuit current up to 50000 A
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Rated fuse current
Fuse
[A]
125
175
Interference voltage category according to EN 61800−3 and motor cable length
Component
c2
EZN3A0022H150
E82ZN75334B230
EZN3A0022H150
E82ZN75334B230
l
Electrical installation
Assignment of mains choke/mains filter
: All classes permissible
rms
: Only classes "J", "T" or "R" permissible
rms
max. [m]
25
50
25
50
Cable cross−section
L1, L2, L3, PE
[AWG]
1/0
2/0
Component
c1
max. [m]
E82ZN75334B230
10
EZN3B0022H150
50
E82ZN75334B230
10
EZN3B0022H150
50
5
179

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis