Herunterladen Inhalt Inhalt Diese Seite drucken

Assignment Of Mains Choke/Mains Filter - Lenze EVS9321 Montageanleitung

Vorschau ausblenden Andere Handbücher für EVS9321:
Inhaltsverzeichnis

Werbung

Installation to UL
Supply conditions
Range
Fuses
Cables
Observe all national and regional regulations!
9300
Type
Operation without mains choke/mains filter
EVS9321−xx
EVS9322−xx
EVS9323−xx
EVS9325−xx
Operation with mains choke/mains filter
EVS9321−xx
EVS9322−xx
EVS9323−xx
EVS9324−xx
EVS9325−xx
EVS9326−xx
Max. connection cross−section of the terminal strip: AWG 12, with pin−end connector AWG 10
5.4.4

Assignment of mains choke/mains filter

9300
Mains choke
Type
EVS9321−xx
EZN3A2400H002
EVS9322−xx
EZN3A1500H003
EVS9323−xx
EZN3A0900H004
EVS9324−xx
EZN3A0500H007
EVS9325−xx
EZN3A0300H013
EVS9326−xx
ELN3−0150H024−001
EDKVS9332X DE/EN/FR 4.0
Standard devices in the power range 0.37 ... 11 kW
Description
l
Only in accordance with UL 248
l
System short−circuit current up to 5000 A
l
System short−circuit current up to 50000 A
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Rated fuse current
Fuse
[A]
6
6
10
25
6
6
10
10
25
25
Interference voltage category according to EN 61800−3 and motor cable length
Component
c2
EZN3A2400H002
EZN3A1500H003
EZN3A0900H004
EZN3A0500H007
EZN3A0300H013
EZN3A0150H024
l
Electrical installation
Assignment of mains choke/mains filter
: All classes are permissible
rms
: Only classes "CC", "J", "T" or "R" permissible
rms
max. [m]
5
5
5
5
5
5
Cable cross−section
L1, L2, L3, PE
[AWG]
18
18
16
10
18
18
16
16
10
10
Component
c1
max. [m]
EZN3B2400H002
50
EZN3B1500H003
50
EZN3B0900H004
50
EZN3B0500H007
50
EZN3B0300H013
50
EZN3B0150H024
50
5
153

Werbung

Inhaltsverzeichnis
loading