Herunterladen Diese Seite drucken

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Bit
Definition
0
position error
1
voltage supply error
2
too high current
3
commissioning diagnostics
4
storage error
5
6
7

3.4.3 Operating status

Octet 9 in the diagnostic function provides information about measuring instrument-specific parameters.
An encoder of class 2 sets the functionality bit for class 2 commands to show the DP master that all
commands of class 2 are supported. The DP master must activate the functionality bit of class 2 in the
parameter message (DDLM_Set-Prm) to enable the use of class 2 functions.
The status bit of the scaling function is set when the scaling function is activated and the resolution of the
encoder is calculated by means of the scaling parameters.
DDLM_Slave-Diag
Octet
Bit
Bit
Definition
0
Code sequence
1
Functionality of class 2
2
Commissioning diagnostics
3
Scaling function status
4
5
6
7
= 0
no
no
no
OK
no
not yet
used
9
7 – 0
operating status
= 0
increasing position values
for clockwise revolutions
(seen from the shaft)
no, not supported
no, not supported
scaling disabled
Not yet
used
56
= 1
yes
yes
yes
error
yes
= 1
increasing position values
for counterclockwise
revolutions
(seen from the
shaft)
yes
yes
scaling enabled

Werbung