3.4 Diagnostic information

The diagnostic information contains diagnostic data which are on the one hand defined in the Profibus-DP
specification (octet 1 to 6) and on the other hand measuring instrument-specific diagnostic data:
Diagnostic function
Station status 1
Station status 2
Station status 3
Diagnostics master address
PNO identification number
Extended diagnostic header
Alarms
Operating status
Type of encoder
Singleturn resolution (encoder)
Measuring unit (length measuring
instrument)
Number of distinguishable revolutions
Additional alarms
Supported alarms
Warnings
Supported warnings
Profile version
Software version
Operating time
Offset value
Offset value of the manufacturer of
the encoder
Measuring units per revolution
Total measuring range (unit)
Serial number
Reserved for future definitions
Limit switch minimum
Limit switch maximum
Data type
octet number
bit
bit
bit
bit
bit
octet string
octet string
octet string
octet string
32 without sign
16 without sign
octet string
octet string
octet string
octet string
octet string
octet string
32 without sign
32 with sign
32 with sign
32 with sign
32 without sign
ASCII string
32 without sign
32 without sign
54
Diagnostics
Device class
1
2
3
4
5 - 6
7
8
9
10
11 - 14
15, 16
17
18, 19
20, 21
22, 23
24, 25
26, 27
28 - 31
32 - 35
36 - 39
40 - 43
44 - 47
48 - 57
58 - 61
62 - 65
special
66 - 69
special
Details
1
-
1
-
1
-
1
-
1
-
1
0
1
0
1
0
1
0
1
0
1
0
2
0
2
0
2
0
2
0
2
0
2
0
2
0
2
0
2
0
2
0
2
0
2
0
2
-

Werbung