Device Installation; Cabling; Address; Terminating Resistor - IFM Electronic RNX-13 Bit Handbuch

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

2 Device installation

2.1 Cabling

The Profibus-DP device is supplied with 10 to 30 V DC by means of the screw terminal strip on the PCB.
A screened power cable should be used. A cable according to the Profibus specifications should be used
as data cable.
For the installation of the encoder with Profibus-DP interface please see the installation instructions
enclosed to the product.

2.2 Address

The address of the Profibus-DP unit must be set to a value between 3 and 126 by means of the respective
address selector switch. The address is set in decimal code (the value for each switch position is marked
beside the switch). The measuring instrument reads the address switch only at power-up.
Note!
The Profibus-DP device does not support the setting of the slave address by the PROFIBUS master.
Setting of the address:
1.
Switch off the power supply to the Profibus-DP unit if necessary.
2.
Set the address by means of DIP switches.
3.
Fix cover according to the installation instructions.

2.3 Terminating resistor

If the Profibus-DP device to be installed is used as last participant in the system, the terminating resistor
on the PCB must be activated. For the position of the switches see the respective installation instructions.

2.4 GSE file

A diskette with the respective GSE files (device identification records) is supplied with the Profibus-DP
manual.
Installation:
4. Select the GSE file of the respective device on the diskette and copy the *.gse file into the respective
directory of the Profibus configuration tool.
5. Select the bitmap file of the respective device on the diskette and copy the *.bmp file into the
respective directory of the Profibus configuration tool.
6. Update the GSE files (SCAN).