3 Installation
3.1 Installation instruction
3.1.1 Mounting
The appropriate installation instructions must be observed for the mechanical
electrical installation. The instruction leaflet (IL04210002E) is included in the
packaging.
•
ZEB12
•
ZEB32
•
ZEB65
•
ZEB150
•
ZEB225A
DANGER
To ensure explosion-proof operation, the motor-protective relay
may only be reset/switched on manually, or automatically via
a control interlock circuit for the motor or electrical machinery,
after the motor has cooled down.
A manual reset may be carried out by trained personnel locally
or in the control room.
DANGER
An automatic restart is particularly not permissible with Ex e
applications after the control voltage has failed and then been
restored.
▶
Mount the overload relay according to the installation instruction.
▶
Wire the motor cables.
1 ~
3 ~
Figure 4: Main circuit wiring
ZEB (XTOE, C440) 11/16 MN03402007Z-DE/EN www.eaton.com
AC
DC
3 Installation
3.1 Installation instruction
39