1. INSTALLATION

This product should be installed by a qualified electrician
1.1 Box Contents
Phoenix Multi, MultiPlus, or Inverter
User manual.
Installation manual.
Bag containing connection items, i.e.:
Temperature sensor.
Fuse (Mega fuse).
Four M8 nuts.
Four M8 washers.
Four M8 spring washers.
Charging current warning sticker.
1.2 Location
The product must be installed in a dry and well-ventilated area, as close as possible to the
batteries. There should be a clear space of at least 10 cm around the appliance for cooling.
Excessively high ambient temperature will result in the following:
Reduced service life.
Reduced charging current.
Reduced peak capacity, or shutdown of the inverter.
Never position the appliance directly above the batteries.
The product is suitable for wall mounting. The back of the enclosure has holes for wall
mounting purposes, see Appendix B.
The appliance can be mounted horizontally as well as vertically; vertical mounting is
preferable. The vertical position offers optimum cooling.
The interior of the product must remain accessible after installation.
Ensure that the AC and DC input cables are fitted with fuses and circuit breakers. Try and
keep the distance between the product and the battery to a minimum in order to minimize
cable voltage losses.
For safety purposes, this product should be installed in a heat-resistant
environment. You should prevent the presence of e.g. chemicals, synthetic
components, curtains or other textiles, etc., in the immediate vicinity.