2.3.7.4 PowerAssist – Boosting the capacity of shore or generator power (default: on)
The feature that distinguishes the Phoenix MultiPlus from the standard Multi is PowerAssist.
This feature takes the principle of PowerControl to a further dimension allowing the
MultiPlus to supplement the capacity of the alternative source. Where peak power is so
often required only for a limited period, it is possible to reduce the size of generator needed
or conversely enable more to be achieved from the typically limited shore connection. When
the load reduces, the spare power is used to recharge the battery.
Note 1: minimum shore current 2 A or generator capacity 2,5 kW required per MultiPlus.
Note 2: Some modern AC generators use a static inverter to generate the AC output. Some
of these generators also reduce rpm when operating with reduced load. By enabling the
Dynamic Current Limit function (VEConfigure) the MultiPlus can be used to assist the
generator when suddenly a high load is connected.
Set the DS 3-7
Switch PowerAssist on or off
Determine whether PowerAssist
DS-8
support should be on or off.
DS-7 on
The default is Off.
DS-6
off
The left-hand LED column is for Off.
DS-5 on
The right-hand LED column is for
DS-4
off
On.
DS-3
off
Press the pushbuttons until the
DS-2
required LED indication is
DS-1
displayed.
Example
Required: PowerAssist is on.
LED indication =
Off
On
19