Set the DS 3-7
Set the charging characteristic
Determine the required charging
DS-8
characteristic:
DS-7
off
1:
DS-6 on
2:
DS-5 on
3:
DS-4 on
mode (default)
DS-3
off
DS-2
Press the pushbuttons until the
DS-1
required LED indication is
displayed.
2.3.6.3 Charge Current
The default charging current is 75% of the maximum charging current. This current will be
too high for most applications. For most battery types the optimal charging current is 0.1-
0.2x the battery capacity.
Set the DS 3-7
Set the charging current
Determine the required charging
DS-8
current Iq.
DS-7
off
Determine the setting number.
DS-6 on
DS-5
off
DS-4
off
DS-3
off
Determine the LED indication.
DS-2
Press the pushbuttons until the
DS-1
required LED indication is
displayed.
Increment size is 1A.
12
Fixed
Adaptive
Adaptive with BatterySafe
Scale = 2A
Offset = 0A
Setting number = Iq/2
Example
Required: charging characteristic
is Fixed.
Setting number = 1.
LED indication =
0
0
0
0
0
0
0
1
0
1
Example
Battery capacity is 450Ah. The
recommended maximum
charging current is 450*0.2 =
90A.
Setting number = 90/2 = 45.
LED indication =
0
0
0
1
2
2
2
2
4
5