Assignment of metering enable

If the metering enable should also be active during the pre-metering, the menu ENABLE
ALSO ON PREMETERING must be set to YES in the CONFIGURATION FUNCTION (set
to NO ex-works)
To select the assignment for metering enable, proceed as follows:
1. Activate the CONFIGURATION FUNCTIONS menu.
2. Press the ↵ key.
3. Scroll with the NEXT key until the next menu is displayed.
4. Switch over from NO to YES by pressing one of the
5. Press the NEXT key to confirm.
7.4.7

Activate separate pre-metering output

If an additional relay output is required for activating a pre-metering pump, this must be
activated by selecting YES under PREMETERING OUT SEPARATE in the
CONFIGURATION FUNCTIONS menu (ex-works setting is NO).
This means the relay output will be activated with the output SP1 during the pre-metering.
To select the separate pre-metering output, proceed as follows:
1. Activate the CONFIGURATION FUNCTIONS menu.
2. Press the ↵ key.
3. Scroll with the NEXT key until the next menu is displayed.
4. Switch over from NO to YES by pressing one of the
5. Press the NEXT key to confirm.
417102012_LMI02.doc
or
or keys.
- 84 -
keys.
Rev. 10-01.09