Displays during operation

7.1.2.1 Displays in AS mode (priming mode)

The conductivity display flashes for conductivity values > 200mS/cm (conductivity value
is outside the selected limit of rated value.
NOTE
If the conductivity and temperature measuring ranges are exceeded, this is indicated by
flashing bars ( - - - )
Without activation of limit values for SP1 and SP2 (for concentration setting "OFF") and for
open metering enable contact (SP1 is blocked).
The activation of limit values SP1 and/or SP2 is displayed with the respective number (SP1
above left, SP2 above right)
The hash symbol (#) indicates that SP1 has been blocked with the help of metering enable
input (open contact). SP1 is released when metering enable contact is switched off and the
hash symbol ((#) is no longer displayed.
The switching on of relay SP1/SP2 is indicated by a triangle (▲) before or behind the
respective number.
If the pre-metering is activated, a rhombus is displayed instead of the hash symbol (#), or a
triangle (▲) (depending upon the configuration) during the pre-metering period.
If a pre-metering delay time has been set, an upward arrow ٨ and a downward arrow ٧ is
displayed instead of the rhombus (◊) for the duration of the delay time.
417102012_LMI02.doc