Herunterladen Inhalt Inhalt Diese Seite drucken

IFM Electronic ecomat 100 Gerätehandbuch Seite 25

Vorschau ausblenden Andere Handbücher für ecomat 100:
Inhaltsverzeichnis

Werbung

Index
S-Idx
Name
E
configuration channel
14
F
configuration channel
15
10
configuration channel
16
2001
0
PWM frequency
20F0
0
CANopen node ID
20F1
0
CANopen node ID
20F2
0
CAN baud rate
20F3
0
CAN baud rate
20F4
0
auto start
2500
0
number of 8bit user
variables
1
8bit user variable 1
2
8bit user variable 2
Type
Default
rw
u8
0x03
rw
u8
0x02
rw
u8
0x02
rw
u8
0x64
rw
u8
0x20
rw
u8
0x20
rw
u8
0x03
rw
u8
0x03
rw
u16
0x00
ro
u8
0x0A
rw
u8
rw
u8
CabinetModul CR2012
Description
0x00 = off
0x01 = binary input
0x03 = analog input absolute
0x06 = analog input ratiometric
0x09 = voltage 0���30,000 mV
0x00 = off
0x01 = binary input
0x02 = binary output + read back
input
0x00 = off
0x01 = binary input
0x02 = binary output + read back
input
0x04 = analogue output (PWM
20���250 Hz)
20��250 Hz
PWM frequency for channel 8
and 16
1���127
The entries 20F0/20F1 must
always contain identical values�
The new entries are valid after
a reset (switching the module
off/on)�
Values outside the permissible
ranges will be rejected�
0 = 1000 Kbaud
1 = 500 Kbaud
2 = 250 Kbaud
3 = 125 Kbaud
4 = 100 Kbaud
5 = 50 Kbaud
6 = 20 Kbaud
The entries 20F2/20F3 must
always contain identical values�
The new entries are valid after
a reset (switching the module
off/on)�
Values outside the permissible
ranges will be rejected�
Time after reaching
Preoperational State to change
to Operational State�
0���5000 ms
0 = auto start deactivated
Idx 2500���2530 = range which
can be freely used for customer-
specific entries
DE