Heatsink Over
Temperature
Alarm code:86
Para Cable Male Loss
Alarm code:E3
Para Cable Female Loss
Alarm code:E4
Para Bat Differ
Alarm code:E6
Para Byp Differ
Alarm code:E8
(PowerWalker VFI
10000TCP 3/1 mode
has no this case)
Para Line Differ
Alarm code:E7
Para Work Mode Differ
Alarm code:E9
Para Rate Power Differ
Alarm code:EA
ECO In Para
Alarm code:EB
Inside temperature of
UPS is too high
The parallel cable is
disconnected
The parallel cable is
disconnected
The battery packs of
some UPSs are
disconnected
The M2 bypass input of
some UPSs is
disconnected
The M1 line input of
some UPSs is
disconnected
There are different
power strategy setting
in parallel system
There are different UPSs
in parallel system
HE function is enabled
in parallel system
52
Check the ventilation of UPS and
the ambient temperature.
Check the parallel cable.
Check the parallel cable.
Check if all the battery pack is
connected.
Check the building wiring and
input cable.
Check if the M2 breaker is closed.
Ensure the UPSs are connected to
same input source.
Check the building wiring and
input cable.
Check if the M1 breaker is closed.
Ensure the UPSs are connected to
same input source.
The UPSs with different power
strategy setting (Ex. one Line
mode and one Converter mode)
are forbidden to parallel.
The UPSs with different capacity
(Ex. one 10KVA and one 20KVA)
are forbidden to parallel.
HE function is forbidden in parallel
system.