10.3 Safety regulations

Type
Internal overvoltage protection
DC insulation monitoring
DC injection monitoring
Grid monitoring
Residual current monitoring unit
Islanding protection
EMC immunity
EMC emission
Utility interference
INFORMATION
If you choose the standard VDE-AR-N 4105, please refer to information below.
If a central network and system protection device is used for power generation
systems, the value of the rise-in-voltage protection U > of 1.1Un presented in the
integrated network and system protection can be changed, but a password is required.
It is not necessary to adjust the value of the displacement power factor cos(phi) if the
power generation system is ΣSAmax ≤ 3.68KVA and was set to 1 as default in the
embedded inverter software. However, if the power generation system is 3.68KVA
<ΣSAmax≤13.8KVA, the standard cos(phi) characteristic curve defined in VDE-AR-N
4105 shall be applied through the PMU.
Installation and Operating Instructions
TL3680
Integrated
Integrated
Integrated
Integrated
Integrated (according to EN 62109-2)
Integrated
EN61000-6-1, EN61000-6-2
EN61000-6-3, EN61000-6-4
EN61000-3-2,
EN 61000-3-3
TL5000-10
EN61000-3-11,
EN 61000-3-12
49