2、If you want to set up other safety regulations, refer to the example for the
Netherlands.

9.2 Display messages

Along with the various operating states, different messages may be shown on the
display as follows.
State
Error
code
Initialization
Normal
Flash
Fault
Installation and Operating Instructions
Description
Waiting
Checking
Reconnect
Normal
F/W Updating
9
GFCI Failure
8
AC HCT Failure
6
High DC Bus
35
Utility Loss
40
Over Temperature
33
Fac Failure
34
Vac Failure
Causes
Initial PV voltage is between Min. DC input
voltage and start-up DC input voltage of the
inverter.
The inverter is checking feed-in conditions
after the initial PV voltage exceeds the
initial DC input voltage of the inverter.
The inverter is checking feed-in conditions
after the last fault has been solved.
The inverter is operating normally.
The MCU firmware is being updated
Ground-fault detection circuit is abnormal
Output current is abnormal.
The voltage of DC bus bar exceeds the
permitted upper limit.
The utility cannot be detected, which may
be caused if no utility grid is available, the
grid is disconnected, the AC cable is
damaged, a fuse is broken or during island
mode.
The internal temperature exceeds the
permitted value.
The grid frequency is outside the permitted
range.
The grid voltage is outside the permitted
range.