CA1/
Trimming of measuring range
The measuring range, and consequently the measured value itself, can be corrected to
CE1
compensate for sensor tolerances to calibrate the instrument for use with other indica-
tors.
CA1 - for trimming at the lower end of the measuring range
CE1 - for trimming at the upper end of the measuring range
PC1 The PC1 resets the trimming performed using CA1/CE1.
Parameters when S5=6/7 (resistance based sensor)
Parameter/Function
Decimal point
Start of scale value
Full scale value
Calibrated value for MA1
Calibrated value for ME1
1)
The decimal point in the measuring range must be observed!
Definition of parameters when SS5=6/7 (resistance based sensor)
MP1 MP1 defines the position of the decimal point for the measuring range.
Definition of measuring range
Method 1: resistance values are known
MA1/
Select MA1 and ME1 parameters and enter known resistance values:
ME1
CA1 and CE1 parameters are ignored.
Method 2: resistance value unknown
CA1/
Calibrate start of scale
CE1
value
Calibrate full scale value
Line resistance is then trimmed automatically; parameters MA1/ME1 are ignored.
SIPART DR19
C73000-B7474-C140-06
Param.-
Min
Max
names
MP1
_.---
MA1
-1999
9999
ME1
-1999
9999
1)
CA1
present output value
1)
CE1
present output value
Set control element to 0% and select CA1 parameter;
Press button
(9) until 0.0 is displayed;
Set control element to 100% and select CE1 parameter;
Press button
(9) until 100.0 is displayed;
Configuring
Factory
Eng.
setting
unit
----
.-
-
---
0,0
100.0
%
%
75