Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens SIPART DR19 Kurzanleitung Seite 62

Vorschau ausblenden Andere Handbücher für SIPART DR19:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Configuring
Config.
Setting
switch
S10
Input signal AI3 (slop 1) with UNI module (only effective when
S9 = 4/5/6/7)
[0]
U[mV] (linear), with range plug I [mA] or U [V]
1
Thermocouple with internal reference junction
2
Thermocouple with external reference junction
3
Pt100 4-wire connection
4
Pt100 3-wire connection
5
Pt100 2-wire connection
Resistance transmitter with R < 600 Ω
6
7
Resistance transmitter with R < 2,8 kΩ
S11
Thermocouple type AI3 (slot 2) with UNI module
(only effective if S10 = 1/2)
[0]
Type L
1
Type J
2
Type K
3
Type S
4
Type B
5
Type R
6
Type E
7
Type N
8
Type T
9
Type U
10
Any type (without linearization)
Take square roof of AI1 to AE3
S12
AI1
S13
AI2
S14
AI3
Allocation of x1, x2, x3, yN, yR, z to AI1A to AI3A
S15
x1
S16
x2
S17
x3/wE
S18
yN
S19
yR
S20
z
62
Function
no
yes
[0]
1
[0]
1
[0]
1
0 %
AI1
AI2
0
[1]
2
0
1
[2]
0
1
2
[0]
1
2
[0]
1
2
[0]
1
2
Quick Reference
AI3A
3
3
[3]
3
3
3
SIPART DR19
C73000-B7474-C140-06