Quick Reference
Config.
Setting
switch
3
Pt100 4-wire connection
4
Pt100 3-wire connection
5
Pt100 2-wire connection
Resistance transmitter with R < 600 Ω
6
7
Resistance transmitter with R < 2,8 kΩ
S6
Thermocouple type AI1 (only effective when S5 = 1/2)
[0]
Type L
1
Type J
2
Type K
3
Type S
4
Type B
5
Type R
6
Type E
7
Type N
8
Type T
9
Type U
10
Any type (without linearization)
S7
Temperature unit AI1 and AI3 with UNI module (only effective when
S5 or S10 = 1/2/3/4/5)
[0]
Degrees Celsius
1
Degrees Fahrenheit
2
Degress Kelvin
S8
Input signal AI2 (slot 2) and transmitter fault signal
[0]
I [0 ... 20 mA]
1
I [0 ... 20 mA]
2
I [4 ... 20 mA]
3
I [4 ... 20 mA]
S9
Input signal AI3 (slot 1) and transmitter fault signal
[0]
I [0 ... 20 mA]
1
I [0 ... 20 mA]
2
I [4 ... 20 mA]
3
I [4 ... 20 mA]
4
UNI-module
5
UNI-module
6
UNI-module
7
UNI-module
SIPART DR19
C73000-B7474-C140-06
Function
or U, R, P, T
or U, R, P, T
or U
or U
or U, R, P, T
or U, R, P, T
or U
or U
min. on sensor breakage
max. on sensor breakage
min. on sensor breakage
max. on sensor breakage
Configuring
without MUF
with MUF
without MUF
with MUF
without MUF
with MUF
without MUF
with MUF
without MUF
without MUF
with MUF
with MUF