onPA - online parameters
Parameter
Filter time constant for xd filter
(adaptive)
Derivative action gain
Vv
Proportional gain
Kp
Integral action time
Tn
Derivative action time
Tv
Response threshold
Working point
Safety setpoint 1
Safety setpoint 2
Safety setpoint 3
Safety setpoint 4
Start of manip. variable scale (YA<YE)
Full scale of manip. variable
Heating period, y positioning time open
Cooling period, y positioning time closed
Actuating pulse interval
Length of actuating pulse
Filter time AI1
Filter time AI2
Filter time AI3
Constant c1
Constant c2
Constant c3
Constant c4
Constant c5
Constant c6
Constant c7
Display refresh rate
1)
If S2=1: up to 9980 ms, minimum pulse interval and length;
with tA in cooling circuit, with tE in heating circuit.
SIPART DR19
C73000-B7474-C140-06
Param-
Min
Max
name
tF
off/1.000
1.000
uu
0.100
10.00
cP
0.100
100.0
tn
1.000
9984
tu
off/1.000
2992
AH
0.0
10.0
Y0
Auto/0.0
100.0
SH1
-10.0
110.0
SH2
-10.0
110.0
SH3
-10.0
110.0
SH4
-10.0
110.0
YA
-10.0
110.0
YE
-10.0
110.0
tP
off/0.100
1.000
tM
off/0.100
1.000
tA
20
600
tE
20
600
t1
off/1.000
1.000
t2
off/1.000
1.000
t3
off/1.000
1.000
c1
-1.999
9.999
c2
-1.999
9.999
c3
-1.999
9.999
c4
-1.999
9.999
c5
-1.999
9.999
c6
-9.99
9.99
c7
+1.000
9.999
dr
0.100
9.900
Configuring
Factory
Eng.
setting
unit
1.000
s
5.000
1
0.100
1
9984
s
off
s
0.0
%
Auto
%
0.0
%
0.0
%
0.0
%
0.0
%
-5.0
%
105.0
%
1.000
s
1.000
s
1)
200
ms
1)
200
ms
1.000
s
1.000
s
1.000
s
0.000
0.000
0.000
1.000
0.000
0.00
1.000
1.000
s