Herunterladen Inhalt Inhalt Diese Seite drucken

Ofpa - Offline Parameters - Siemens SIPART DR19 Kurzanleitung

Vorschau ausblenden Andere Handbücher für SIPART DR19:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Configuring
3.2

oFPA - Offline parameters

Parameters determining basic functions, such as display elements, limit values,
Contents
safety values etc.
Step
Accessing
1
Press button
the oFPA list
"onPA" (selection level) displayed. Blocked if digital signal bLPS = 1.
2
Press button
level). Blocked if digital signal bLS=1.
3
Press button
(configuring level). Controller now blocked and last value of y retained.
Selection and
4
Using buttons
modification
digital indicator.
of parameters
5
Press button
tons 7, 8 operate on PV-X.
6
Using buttons
indicator.
7
Press button
switched back.
8
Repeat steps 4 to 7 until all desired parameters are set.
Exit to pro-
9
Press button
cess control
10
Press button
level
manual mode.
oFPA - offline parameters
Parameter
Decimal point. x- and. w-indicator.
Scale start value
Full scale value
Alarm 1
Alarm 2 (A2 < A1)
Alarm 3
Alarm 4 (A4 < A3)
Alarm hysteresis
58
Procedure
(6) about 5 sec until "PS" flashes. Release button -
(8) several times until "oFPA" is displayed selection
(9) about 3 sec until digital indicator SP-W (2) flashes
(7) or
(8). Select parameter names in the SP-W (2)
(6) once, indicator PV-X (1) flashes. Adjustment but-
(7) or
(8) Modify parameter values in the PV-X (1)
(6) once, indicator SP-X (2) flashes, input field is
(13) once (selection level).
(13) once (process control level). Controller is now in
Param.-
Min
Max
name
dP
_.---
dA
-1999
9999
dE
-1999
9999
A1
A2
-110 % to110 % of dA, dE
A3
with S83/S84= 0/2/3/4/5
A4
HA
0.1
10.0
Quick Reference
Factory
Eng.
setting
unit
---
_.-
-
0.0
100.0
5.0
-5.0
5.0
-5.0
1.0
%
SIPART DR19
C73000-B7474-C140-06

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis