Configuring
Parameters when S5=0/1/2/3/4/5 (U/I/thermocouples/Pt100)
Parameter/Function
Reference junction temp.
Line resistance (RL)
Trim value RL
Decimal point
Start of measuring range
End of measuring range
Trimming in lower measuring range
Trimming in upper measuring range
Reset trim values
1)
Only displayed when S5 = 2
Definition of parameters when S5=0/1/2/3/4/5 (U/I/thermocouples/Pt100)
tb1
External reference junction temperature for thermocouples.
Trimming of line resistance with Pt100 in two-wire circuit
Mr1
Method 1: line resistance is known
Select Mr1 parameter and enter known line resistance: Cr1 parameter is ignored.
Cr1
Method 2: line resistance unknown
Short-circuit Pt100 at point of measurement;
Select Cr1 parameter
Press button
(9) until 0.00 is displayed;
Line resistance is then trimmed automatically;
Mr1 shows line resistance measured.
MP1 MP1 defines the position of the decimal point for the measuring range.
MA1/
Definition of measuring range
with thermocouples or directly connected Pt 100s (S5=1/2/3/4/5)
ME1
The values are entered directly in ºC/ºF/K (S7=0/1/2).
If the selected temperature measuring range is to be displayed on the front panel, the
Offline parameters dA and dE must be equal to the CAE1 parameters MA1 and ME1.
in the case of: mV, U or input signals (S5=0)
The values are entered in mV (-175 mV to +175 mV);
The U or I input signals are converted to a measuring range of 0/20 to 100 mV in the
measuring range plug (6DR2 805-8J)
Example:
0 to 10 V or 0 bis 20 mA:
2 to 10 V or 4 bis 20 mA: MA1=20, ME1=100
74
Param.-
Min
Max
names
1)
tb1
0
400.0
2)
Mr1
0.00
99.99
2)
Cr1
Difference to Mr
MP1
_.---
----
MA1
-1999
9999
ME1
-1999
9999
CA1
present measured value
CE1
present measured value
PC1
no/no C/YES
2)
Only displayed when S5 = 5
MA1=0, ME1=100;
C73000-B7474-C140-06
Quick Reference
Factory
eng.
settings
unit
50
°C/°F/K
10
.-
-
---
0.0
mV/°C/°F/K
100.0
mV/°C/°F/K
mV/°C/°F/K
mV/°C/°F/K
no C
-