7 Service menu of the RLS 45 K (for the specialist installer)
Parameter 5: 230 VAC input
Parameter 6: Sensors
Parameters for using the connected internal and
external sensors. The internal sensor PP 45 HYI
and the external sensors PP 45 HY, PP 45 CO2
and PP 45VOCare available.
26
1 = Sleep mode
2 = Intermittent ventilation
3 = Safety shutdown
4 = Supply air mode without
overrun, for volumetric flow
compensation for exhaust
air fans (ECA/ER (60m³/h))
5 = Supply air mode with
overrun of 6 minutes
6 = Supply air mode with
overrun of 15 minutes
4 to 6: Activate volumetric
flow compensation using
RV 2 units additionally via
commissioning software.
230 V input with switching
contact, additional function
can be used with button or
switch, see Connection and
wiring diagram, "S1".
Recommendations: Use a
button for the sleep mode
and intermittent ventilation
functions (reacts to falling
edge).
Use a switch for functions 3
to 6 (reacts to switching
status).
0 = No sensors
1 = 1x internal sensor, no
external sensor
2 = 1x internal sensor, 1x
external sensor
3 = 1x internal sensor, 2x
external sensor
4 = 1x internal sensor, 3x
external sensor
5 = 0x internal sensor, 1x
external sensor
6 = 0x internal sensor, 2x
external sensor
7 = 0x internal sensor, 3x
external sensor
Parameter 7: EnOcean
Parameter 8: EnOcean Teach mode
No function for RV 2.
Parameter 9: Number of PPB 30 K units
No function for RV 2.
Parameter 10: ModBus settings
ATTENTION: The ModBus interface must be de-
activated for RV 2 units, otherwise RV 2 units
cannot be controlled.
Parameter 11: ModBus address
No function for RV 2.
Parameter 12: Plug & Play
Exit setting mode
Press the
and
seconds. The ventilation unit switches to the spe-
cified ventilation level.
For activating the EnOcean
extension module PP 45
EO.
0 = EnOcean module not
present
1 = Activate EnOcean mod-
ule
Automatic search run for
pairwise assignment of the
supply air and exhaust air
units.
0 = Manual settings with
CDV commissioning soft-
ware
1 = Plug & Play: Start auto-
matic search
For further information →
following chapter.
buttons together for 5