Operation
Remote control panel
Defrost
28
Automatic Defrost: During automatic defrost,
plete, the heat pump will return to the previously selected mode .
Manual Defrost: To initiate forced defrost mode, the compressor must have been running in
heating mode for at least 10 minutes .
The interval between forced defrosts should be at least 35 minutes .
Press and hold both
flash during the defrost process .
Do not use any other means to accelerate the defrosting process or to clean the evaporator .
INFO
During a normal defrost cycle, the heat pump may release significant amounts of vapour or
mist into the air .
After a power cut, the heat pump may restart automatically when power is restored due to its
power-down memory feature .
Electrical storms can damage the electronic circuits in the heat pump . It is recommended to
isolate the heat pump from the mains power supply if a storm is expected .
will flash . Once the defrost cycle is com-
and
for five seconds to start the forced defrost .
Operation: Remote control panel
will