Instruction manual
5.5
Digital communication
5.5.1
P19 HART short address (device address)
FACTORY DEFAULT: 0
A unique device address by which the device is identified and managed via HART.
P19
Device Identification ➙ HART Device Short Address
EView2
Description
0
Analog current loop output is active (current transmission via
4...20 mA)
15
Analog current loop inactive (no current transmission, fixed 4
mA), multi-drop
5.6
Measurement optimization
5.6.1
P20 Damping Time
FACTORY DEFAULT: 40
Damping time reduces unwanted fluctuations in displaying the measured data (e.g., ripples). If the level jumps, the transmitted value
reaches 98% of the jump at this time. Unit: second (s). Value range: 0...999 s.
P20
EView2
Barely or non-volatile/
waving media
Highly volatile /
strongly waving liquid
Damping example 1
Damping time = 10 s
Level change (level) = 2 m (6.6 ft)
Measurement optimalization ➙ Damping time
Damping Time
For testing
0 s
> 6 s
Recommended
2 s
> 10 s
Damping time = 40 s
Level change = 2...3 cm (0.39"...0.79") ripple If a higher degree of
undulation is expected in the measured liquid column, it is
recommended to set a higher damping time. This way, the
fluctuation of the value of the transmitted level can be reduced.
Type 2298 80 GHz Radar Level Sensor
Damping example 2
33