Type 2298 80 GHz Radar Level Sensor
5.4.2
P14 Relay parameter – Relay on value
FACTORY DEFAULT: 0
The measured PV value at which reaching the upper limit value is indicated on the RELAY output.
Adjustable value range: Value is adjustable according to PV setting range.
P14
Outputs ➙ Relay output ➙ Relay parameters ➙ Energized
EView2
value
5.4.3
P15 Relay parameter – Relay off value
FACTORY DEFAULT: 0
The measured PV value at which reaching the lower limit value is indicated on the RELAY output.
Adjustable value range: Value is adjustable according to PV setting range.
P15
Outputs ➙ Relay output ➙ Relay parameters ➙ De-
EView2
Energized value
5.4.4
P16 Relay parameter – Relay off value
FACTORY DEFAULT: 0
If the PV measurement value has reached the lower or upper switching value or an error has occurred in the case of an error signal,
the actual RELAY operation is activated after this time, or after this time, a change is visible on the output.
Adjustable value range: 0...999 s.
P16
Outputs ➙ Relay delay time
EView2
5.4.5
P17 Relay parameter – Flow parameter value
FACTORY DEFAULT: 1
In the case of FLOW, the relay gives a pulse per volume unit specified here. The volume unit is set in parameter P13:c. The pulse width
is 100 ms.
The guaranteed maximum pulse density: < 3 seconds.
P17
Outputs ➙ Relay output ➙ Relay parameters ➙
EView2
Pulse constant
32