  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 125
46
5. Read out the pressure drop Δp inside the heat exchanger that is required for a desired
volume flow from the airflow diagram. The pressure drop Δp is located on the unit
(--- = supply air, - - = extract air).
80
70
60
50
40
30
20
10
0
0
20
40
Fig. 54: Airflow diagram
6. Mount a ball pump needle on each of two hoses of equal length.
Ball pump needle:
7. Connect the hoses to the ΔPa measuring device.
8. Push the needles completely through the rubber cover of P3 and P4 (operation mode  A,
see figure) or P1 and P2 (operation mode B).
Fig. 55: Calibrating the extract air, operating mode A
9. Follow the instructions in the PC tool and adjust the speed of the exhaust air fan until the
ΔPa measuring device indicates the value from step 5.
INSTALLATION AND SERVICE MANUAL FOR PROFESSIONALS
60
80
100
120
Installation: Initial start-up and calibration
P1-P2 (A)
P3-P4 (B)
P3-P4 (A)
P1-P2 (B)
140
160
180
200
220
240