INSTALLATION AND SERVICE MANUAL FOR PROFESSIONALS
Installation: Assembly
5. Route the condensate drain hose in a way that a siphon is created that is at least
A
6. Fill the siphon with at least 0.5 l of water.
7. When routing the siphon directly under the unit, use the hose clamp supplied. To do so,
8. Guide the hose to a drain and make sure it is not exposed to frost. Install a heating cable
9. Ensure a minimum inclination of 1 % (1 cm/metre).
100 mm high. The siphon can be created in two ways:
A) directly under the unit (suitable for most wall installations) or alternatively
B) at the end of the drain hose (suitable for floor installations)
B
Fig. 49: Creating a siphon
fix the hose clamp in the opening on the underside of the unit and guide the
condensate drain hose through the hose clamp to create a siphon.
Fig. 50: Using the hose clamp
around the drain hose if the insulation is not sufficient to provide a frostproof drain
hose.