11.1. Shut down
Temporary shut down
To prevent stagnation, the NeoSoft 2500 Connect regenerates after 3 days, even if the capacity is not completely exhausted. This effective-
ly prevents water stagnation. It is not necessary to shut down your product temporarily.
Leave your NeoSoft connected to the power and water supply. The appliance thus remains in a hygienically safe operating state in accor-
dance with DIN EN 19636-100.
Shut down
If you still want to take the NeoSoft 2500 Connect out of operation temporarily, close the bypass valve of the NeoSoft and de-energize the
system. If the system is later put back into operation, the system must at least be thoroughly flushed and a manual regeneration must be
triggered.
In the event of longer downtimes, the system must be recommissioned by trained specialist personnel.
11.2. Disassembly
Disassembly of a water softener is an intervention in the drinking water installation that may only be carried out by appropriately trained
specialist personnel. Therefore, please commission a licensed specialist company with the disassembly.
11.3. Disposal
If no take-back or disposal agreement has been made, recycle the dismantled components:
Scrap metals
Send plastic elements for recycling
Nominal pressure
Operating pressure
Operating temperature
Ambient temperature
Medium
Nominal capacity Eco
Nominal capacity Standard
Nominal capacity Power
Regeneration time
Nominal flow rate according to DIN 14743
Nominal flow rate according to DIN 19636 from 20 to 8° dH
Pressure loss at nominal flow rate
Resin quantity
Salt consumption per regeneration
Salt supply
Total waste water volume per regeneration
Application range
Power supply
Device voltage pannung
Power consumption
11. Shut down
12. Technical Data
Unit
PN 10
bar
min. 2; max. 8
°C
min. 5; max. 30
°C
min. 5; max. 25
Drinking water
m
x °dH
8
3
m
3
x °dH
15
m
x °dH
22
3
min
25 - 35
m
3
/h
1,5
m
/h
2,3
3
bar
1,0
Liter
7,5
kg
0,2 - 0,95
kg
40
Liter
23 - 33
1 - 3 Residential units
V / Hz
230 / 50
V / DC
12
W
max. 30
35

Werbung