Installation
Removing the Grille
Insert a small tool (no larger than 1.5 millimeters in diameter) through the grille perforation at the edge of the grille and pull to
disengage the grille.
CAUTION: Do not use a screwdriver to pry the grille from the enclosure. This could result in damage to the loudspeaker.
Safety and Regulatory Compliance
The FreeSpace FS2P loudspeaker has passed testing and complies with the following specifications and uses:
Listed to ANSI/UL 1480A-2016, Speakers for Commercial & Safety Professional Use
General-Purpose Use – UL Category UEAY, File Number S36835.
Suitable for use indoors in dry locations.
EN 54-24: 2008, Loudspeaker for Voice Alarm Systems for Fire Detection and Fire Alarm Systems for Buildings
Environmental: Type A (indoor applications)
Suitable for installation using Class 1, Class 2, or Class 3 wiring methods in accordance with NFPA 70, National Electric Code, 2002, Article
640.
Suitable for use with fire alarm circuit wiring methods in accordance with NFPA 70, National Electric Code, 2002, Article 760.
NFPA 70, National Electric Code, 2002, Article 300-22 (c).
NFPA 90-A, 2002, Installation of Air Conditioning and Ventilation Systems, Paragraph 4.3.10.2.6.5.
EMC Directive 89/336/EEC and Article 10 (1) of the directive, EN50081-1 and EN50082-1 as signified by the CE mark.
The FreeSpace FS2P loudspeaker has been designed to the requirements defined in the following European regulatory specification for
combination systems:
British Standard Code of Practice BS 5839, Part 8, when used with the ceramic terminal block and thermal fuse.
Tested to IEC60268-5.
EN 54-24 Certified Ratings
1
Frequency Range
100 Hz to 10 kHz
Sensitivity (1 W @ 4 m)
70.3 dB
Measured Max. SPL @
79.5 dB
4 m
Coverage Angle Octave
500
Band (Hz)
Horizontal Coverage
360°
Vertical Coverage
360°
Rated Impedance
70V
100V
Passive Nominal
16 Ω
Impedance
Rated Noise Power
16W
EN 54-24 Equalization
Type
PEQ
Footnotes
1.
The specifications data was measured in an anechoic chamber,
free-field. Reference plane is on the grille surface and perpendicular
to the reference axis. Reference axis is perpendicular to center of
grille surface. Horizontal plane is containing the reference axis and
perpendicular to the reference plane.
On-axis Frequency Response
90
85
With EN 54-24 EQ
80
applied
75
70
65
60
55
50
45
40
35
20
100
6 • English
1000
2000
4000
190°
120°
123°
190°
115°
120°
1W
2W
4W
4900 Ω
2450 Ω
1225 Ω
5000 Ω
2500 Ω
Freq
Gain
Q
10900 Hz
–12 dB
10
1000
Frequency (Hz)
8W
16W
Loudspeaker for voice alarm systems for fire detection and fire
613 Ω
306 Ω
1250 Ω
625 Ω
For DOP 841029, see boseprofessional.com/FS2PDOP
BW
0.144
10000
boseprofessional.com
0843
2821
Bose Professional
117 South St, Hopkinton, MA 01748 USA
24
DOP 841029
EN 54-24: 2008