English
Bosch Power Tec GmbH
Earthing cables (to the mounting plate (1) /to the
6.31:
door channel (2))
■
One earthing cable each is installed: between the
mounting plate (connection terminals) and the
housing, and between the door channel and the
housing.
6.15.2 Installing the side panels
▶
Procedure
1. Place the side panel next to the housing with the
inner side facing rearwards
2. Use the 8 mm spanner to connect the side panel
earthing cable to the housing with an M5 hex nut
(tightening torque 2.5 Nm + 0.2 Nm max.)
3. Before fitting the side panel: check whether the
rear wall, which is earthed in the factory, is
earthed with an earthing cable (see the figure
below)
Installation | 93
(1)
(2)
Storage system | Installation manual