The external cabling is complete.
As an option, you can connect other external
components (Connecting external components
(optional), p. 107). After connecting the cables to all
components, you can commission the storage system
(Commissioning, p. 111).
7.3
Connecting external components
(optional)
External components are connected to the storage
system via the connector block in the housing. You
can connect the following components:
PV sensor
Computer or LAN
Info: If you do not connect a PV sensor, insert a
resistor (120 Ω 0.25 W 1%) in the CAN Open terminal
(2).
CAN
V-CAN
Open
(1)
(2)
7.5:
Connector block behind the housing door
[1]
V-CAN
CAN bus terminal for analysis tools (e.g.
InverterSetup). On delivery of the storage system, a
terminating resistor is fitted to this terminal.
[2]
CAN Open
Terminal for the PV sensor (optional)
[3]
LAN
Ethernet network terminal
[4]
RS485
Terminal for the energy meter
LAN
RS485
USB
(4)
(3)
Storage system | Installation manual
External cabling | 107
USB
(5)