Display
Parameter name
1.YFCT
1)
2.YAGL
2)
3.YWAY
4.INIT
5.SDIR
6.TSI
3)
7.TSD
8.SFCT
09.SL0
10.SL1
4)
usw. bis
28.SL19
(exemplarisch)
29.SL20
30.DEBA
31.YA
32.YE
33.YNRM
34.YCLS
35.YCDO
36.YCUP
5)
37.BIN1
5)
38.BIN2
6)
39.AFCT
40.A1
41.A2
6)
42. FCT
43. TIM
44. LIM
45.PRST
46.FSTY
47.FSTI
48.FSVL
49.STNR
1)
If "turn" is selected, you cannot set 33°
2)
Parameter does not appear if 1.YFCT=turn has been selected
3)
if TSI= AUto not active
4)
Turning points only appear wih selection 8.SFCT = FrEE
Function
Type of actuator
Rated angle of rotation of feedback
Set transmission ratio selector (7) appropriately
(see view of device)
Stroke range
(Setting optional)
If used, must match set leverage ratio on
the actuator
Driver pin must be set to the value of the actuator
travel or, if this value is not scaled, to the next
larger scale value.
Initialization
Setpoint direction
Setpoint ramp OPEN
Setpoint ramp CLOSE
Setpoint function
Equal-percentage 1: 25, 1:33, 1:50
inverse Equal-percentage 25:1, 33:1, 50:1
Freely adjustable
Setpoint turning point at 0%
5%
usw. bis
95%
100%
Dead zone of controller
Start of manipulated variable limiting
End of manipulated variable limiting
Standardization of
To mech. travel
manipulated variable
Tight closing with manipulated variable
Top and bottom
Value for tight closing below
Value for tight closing above
Function of BI 1
Only message
Block configuring
Block configuring and manual
Drive valve to position up
Drive valve to position down
Block movement
Function of BI 2
Only message
Drive valve to position up
Drive valve to position down
Block movement
Without
A1=min. A2=max
Alarm function
A1=min. A2=min
A1=max. A2=max
Response threshold of alarm1
Response threshold of alarm 2
Function of alarm output
on fault
Fault + not automatic
Fault + not automatic + BI
("+" means logical OR operation)
Monitoring time for setting of alarms
Response threshold of alarm
Preset (factory setting)
"no" nothing activated
"Strt" start of factory s etting
"oCAY" display after pressing key for 5 s
CAUTION: preset results in "NO INIT"
Safety position:
parameterized safety setpoint
last setpoint
open venting valve
Monitoring time for setting the safety position
Safety setpoint
Station number
Parameter values
turn (part-turn actuator)
WAY (linear actuator)
LWAY (linear actuator
without sine correction)
90°
33°
oFF
5 | 10 | 15 | 20
(short lever 33°)
25 | 30 | 35
(short lever 90°)
40 | 50 | 60 | 70 | 90 | 110 | 130
(long lever 90°)
no / ###.#
Strt
rising
riSE
falling
FALL
AUto
0 to 400
0 to 400
Lin
Linear
1 : 25
1 : 33
1 : 50
n1 : 25
n1 : 33
n1 : 50
FrEE
0.0 to 100.0
AUto
0.1 to 10.0
0.0 to 100.0
0.0 to 100.0
MPoS
To flow
FLow
no
Without
uP:
Top only
Bottom only
:dW
uP:dW
0.0 to 100.0
0.0 to 100.0
None
oFF
on
-on
bLc1
bLc2
uP
-uP
doW
-doW
StoP
-StP
None
oFF
on
-on
-uP
uP
doW
-doW
StoP
-StP
oFF
0.0 to 100.0
0.0 to 100.0
AUto
0 to 100
AUto
0.0 to 100.0
no
Strt
oCAY
FSVL
FSSP
FSAC
1 bis 100
0.0 bis 100.0
0 bis 126
5)
action with opened switch or Low level (normally closed)
NC contact means:
action with closed switch or High level (normallly open)
NO contact means:
6)
High level without fault
normal means:
Low level without fault
inverted means:
Factory setting
Unit
WAY
Degrees
33°
mm
oFF
no
riSE
0
s
0
s
Lin
0.0
5.0
usw bis
%
95.0
100.0
%
AUto
%
0.0
100.0
%
MPoS
no
0.0
%
%
100.0
oFF
oFF
oFF
10.0
%
90.0
%
s
AUto
%
AUto
no
FSVL
s
30
0.0
%
126
Customer
setting