4.
Switch to the following display with the mode key
5.
Start initialization by pressing the
During the initialization process "RUN1" to "RUN5" appears one after the other in the lower display.
.
Note
The initialization process can take up to 15 min. depending on the actuator.
Initialization is complete when the following display appears:
The upper value shows the total angle of rotation of the actuator (for example 93.5°).
After you have pressed the mode key
To exit Configuration mode, press the mode key
is displayed. After you have released the mode key, the unit is in manual mode. Pressing the mode key
briefly, you set the positioner back to the automatic mode.
If you want to set further parameters, refer to the leaflet "Operation -- a concise overview" (see page 47
following) or the Manual.
You can start reinitialization from manual or automatic mode at any time.
8
Conformity
The versions of the SIPART PS2 EEx d positioner including the associated options are approved as standard
for operation in zones 1 and 2 as EEx d (see prototype test certificate PTB 99 ATEX1101).
Warning
!
In zones with potentially explosive atmospheres, the positioner may only be supplied with electrical
energy when the housing is corretly closed.
42
:
key for more than 5 s.
briefly, the following display appears:
for more than 5 s. After about 5 s, the software version